Customization: | Available |
---|---|
Type: | Water-Cooled |
Cooling Method: | Water-cooled |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Water Chiller With Convertor
The frequency conversion control system of water chiller with convertor can realize stepless adjustment from 1% to 100%, so that the compressor is always at the optimal speed, thereby increasing the energy consumption ratio, and saving 20% to 30% compared with ordinary screw chillers.
It is widely used in plastics, electronics manufacturing, electroplating, pharmaceutical and chemical, ultrasonic cooling, printing and other industrial productions. It can precisely control the temperature required for modern industrial manufacturing and largely improve efficiency and product quality.
Suitable for various industries
Industrial water chiller is to provide a cooling process in plastic molding, to improve quality of molded products and shorten period of injection molding cycles. Hence maximizes productivity of plastic molding manufacturing.
Model | UNIT | XC-L30WS | XC-L40WS | XC-L50WS | XC-L60WS | XC-L80WS | |
Refrigerating Capacity | KW | 88 | 118 | 152 | 172 | 230 | |
Kcal/h | 75680 | 101480 | 130720 | 147920 | 197800 | ||
Input Power | KW | 22 | 30 | 37 | 45 | 60 | |
Control Type | Externally balanced thermal expansion valve | ||||||
Refrigerant | R22 (R407C) | ||||||
Compressor | Type | Semi-closed screw type | |||||
Quantity | 1 | 1 | 1 | 1 | 2 | ||
Startup Mode | Y-△start | ||||||
Capacity Control | 0-25-50-75-100 | ||||||
Power | 3PH-380V/50HZ (200V/220V/415V 50HZ/60HZ) | ||||||
Evaporator | Type | Dry shell and tube | |||||
Cooling Water Flow (m3/h) | 19 | 21 | 26 | 30 | 39 | ||
Water Pipe Diameter (Inch) | 3\" | 3\" | 3\" | 3\" | 4\" | ||
Condenser | Type | Shell and tube | |||||
Cooling Water Flow (m3/h) | 21 | 26 | 33 | 40 | 45 | ||
Water Pipe Diameter (Inch) | 3\" | 3\" | 3\" | 3\" | 4\" | ||
Safety Protection | Compressor overheat protection, overcurrent protection, high and low pressure protection, over temperature protection, flow protection, phase sequence/phase loss protection, exhaust overheat protection, antifreeze protection | ||||||
Dimensions (L*W*H) | mm | 2145*800*1670 | 2340*800*1670 | 2340*800*1670 | 2580*800*1720 | 3130*900*1860 | |
Weight | KG | 750 | 850 | 950 | 1150 | 1580 | |
Unit Exchange | 1kw=860Kcal/hr 1RT=3024Kcal/hr 1Btu/hr=0.252Kcal/hr |
The chiller is used in the plastic processing machinery mold cooling, electroplating industry,machinery industry, building industry, vacuum coating and food industry,etc.